Inquiry
Form loading...
Products Categories
Featured Products

Vacuum Circuit Breaker(VCB)12KV 24KV 36KV ZW32-12 outdoor AC vacuum circuit breaker

ZW32-12 model outdoor AC vacuum circuit breaker
ZW32-12 model outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit current in 12/24kV, 50/60Hz power system. It is applicable for substations, industry and mining, urban and rural electricity power networks, especially for occasions with frequent operation and automatic power distribution.

    Product Description

    ZW32-12 outdoor AC vacuum circuit breaker

    Product Description

    ZW32-12 model outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit current in 12/24kV, 50/60Hz power system. It is applicable for substations, industry and mining, urban and rural electricity power networks, especially for occasions with frequent operation and automatic power distribution network. It accords with the standard of IEC622 71-100 & GB1984: AC high voltage circuit breaker, IEC60694 & GB/T11022: HV General technical requirement of switch and control apparatus

    Service condition

    1. Altitude: ≤ 2000m;

    2. Ambient temperature: -40°C~+45°C

    3. Wind speed: 34m/s

    4. Earthquake intensity: ≤8 degree

    5. Ambient pollution: IV 

    6. Ice thickness: 10mm

    7. Applicable occasions should be free from inflammables, explosives, corrosives and severe vibrations.

    Product technical parameter

    Name

    Unit

    Data

    12kV

    Rated voltage

    KV

    12

    Rated current

    A

    630,1250

       Rated 

    insulating 

    level

      1min.PF

    withstand voltage

     dry

     KV

     42(across open contacts:48)

     wet

     34

      Lightning   impulse

    withstand voltage(peak)

     kv

     75(across open contacts:85)

    Rated short-circuit breaking   current

    KA

     20,25

    Rated short-circuit making   current (peak)

    KA

     50,63

    Rated peak withstand   current

    KA

     50,63

    4s rated short-time withstand   current

    KA

     20,25

    Rated operating sequence

     

    O-0.3s-CO-180s-CO 

    Breaking times of rated   short-circuit

    breaking current

     times

     30

    Mechanical duration

     times

     10000

    Rated   voltage of energy storage motor

     V

    DC or AC220,DC110, 48, 24 

    Rated operation voltage

     V

     DC or AC220,DC110, 48,24

    Abrasions thickness of contacts

     mm

    Rated current of over-current   release

     A

       Current transformer ratio

     

    200/5, 400/5,   600/5 

    (Protection degree:  class,   Class: 0.5)