Vacuum Circuit Breaker(VCB)12KV 24KV 36KV ZW7-40.5 outdoor vacuum circuit breaker

ZW7-40.5 series outdoor high vacuum circuit breaker
AC 50Hz, rated voltage of 40.5kV outdoor high-voltage electrical equipment. Spring mechanism attached to or electromagnetic actuator can remote control electrical sub, sub-gate can also be storage place manually, manually opening and closing. design performance meet GB1984-2003 AC voltage circuit breaker as the national standard,

    product detail

    Product Description

    ZW7-40.5 outdoor vacuum circuit breaker

    Product Description

    ZW7-40.5 series outdoor high vacuum circuit breaker phase AC 50Hz, rated voltage of 40.5kV outdoor high-voltage electrical equipment. Spring mechanism attached to or electromagnetic actuator can remote control electrical sub, sub-gate can also be storage place manually, manually opening and closing. design performance meet GB1984-2003 AC voltage circuit breaker as the national standard, and meet IEC-56 high voltage AC circuit breakers IEC standards .ZW7-40.5 Type vacuum circuit breaker is mainly used for outdoor 35kV power transmission system control and protection also applies to urban and rural power distribution networks and industrial and mining enterprises in the normal operation and short circuit protection purposes. The product overall structure of the pillars for the vase style on insulator mounted within the vacuum interrupter, the main column under the porcelain vase porcelain vase. for frequent operation place. It have good sealing, anti-aging, high pressure, no burning, no explosion, long service life, installation and maintenance and convenient.

    Environment condition

    1.Ambient Temperature: -40 - +40 

    2. Altitude:≤1000m (if the altitude increased, then the insulation must be higher)

    3. Wind Pressure: no more than 700Pa (equal to 34m/s wind speed)

    4. Earthquake Level: no greater than 8

    5. Pollution Level: IV

    6. Maximum Temperature Drop: no more than 25°C

    Technical parameter

    Name

    Unit

    Data

    Rated Voltage

    kV

    40.5

    Rated Insulation Level

    1Min Power Frequency withstand Voltage

    Dry

    95

    Wet

    80

    Lightning Impulse withstand Voltage(Peak)

     

    185

    Rated Current

    A

    630; 1250; 1600 ; 2000

    Rated Short-circuit Breaking Current

    KA

    20; 25;31.5; 40

    Rated Operating Sequence

     

    O-0.3s-C0-180s-CO

    Rated Short-circuit Opening Times

    Times

    20

    Rated Short-circuit Closing Current(Peak)

    kA

    50;63;80

    Rated Peak withstand Current

    20;25;31.5

    Rated Short Time withstand Current

    kA

    31.5

    Rated Short-circuit Duration

    s

    4

    Average Closing Speed

    m/s

    0.7±0.2

    Average Opening Speed

    1.5±0.2

    Closing Time

    ≤150

    Opening Time

    ≤60

    Mechanical Life

    Times

    10000

    Rated Operating Voltage and Auxiliary   Circuit Rated Voltage

    V

    AC/DC110/220

    DC Current Resistance of Each Phase   (Without transformer)

    μΩ

    ≤100

    Weight

    KG

    1100