SF6 circuit breaker LW34-40.5 T630-20 outdoor load break switch 40.5KV
The circuit breaker is suitable for continuous outdoor operation in tropical areas with the following atmospheric characteristics:
Altitude: 2000m above means sea level
Pollution: Heavy saline atmosphere
Humidity: Up to 90%
Ambient temperatures of +30°C average, (+40°C Max. and -1°C Min.)
Technical parameter
Item |
Unit |
Data |
Rated voltage |
KV |
35 |
Rated power frequency |
Hz |
50/60 |
Rated current |
A |
630 |
Rated power frequency withstand voltage (1min) KV |
Isolating |
95 |
To ground |
95 |
|
Rated lightning impulse withstand voltage (1min) KV |
Isolating |
185 |
To ground |
185 |
|
Rated short-time withstand current(3s) |
KA |
20 |
Rated short-circuit making current(peak) |
KA |
50 |
Phase to phase spacing |
mm |
340 |
Opening time |
sec |
<2 |
Closing time |
sec |
<2 |
Rated line-charging breaking current |
A |
25 |
Rated SF6 gas pressure(20℃) |
Mpa |
0.07 |
SF6 gas leakage rate(yearly) |
Mpa |
≤1% |
Gas moisture content |
ppm |
≤150 |
Mechanism life |
times |
5000 |
Creepage distance |
mm |
372 |
Control system voltage |
V |
220DCV/ACV |
Mass of filled SF6 gas |
Kg |
0.5 |
Mass of equipment |
Kg |
200 |
Dimension W*D*H |
mm |
1400*1200*800 |