ZCW10-72.5 3150-31.5 outdoor load break switch 72.5KV

    ZCW10-72.5/L open-type combined electrical apparatus is a complete set of combined electrical apparatus using air as external insulation SF6 gas as arc extinguishing medium. For the control and protection of three-phase AC 72.5KV transmission and distribution system, it can also be used for connecting circuit breakers and opening and closing capacitor banks. It is suitable for urban substations, enterprise substations and mountain substations with land shortage.

    Structural characteristics

    The circuit breaker, isolating switch, grounding switch, current transformer, bus and other components are organically combined on the grounded steel structure support, which has a compact structure. It occupies only 30%-50% of the space of the split type, and has significant characteristics such as saving land and reducing project cost. The entire interval is prefabricated in the factory, and all the assembly and debugging are completed before the factory, and the whole is transported to the installation site, which greatly reduces the installation cycle. The use of fully verified high-performance arc extinguishing chamber, isolation switch, basically no maintenance, high reliability. The factory prefabricated self-supporting busbar in the compartment does not require the user to repair the frame. Flexible layout, can be used for a variety of wiring methods. The circuit breaker can be repaired or replaced as a whole, and the power failure time can be reduced to less than 3 hours due to body failure.

    Technical parameter

    Item

    Unit

    Data

    Rated voltage

     KV

     72.5

    Rated power frequency

     Hz

    50/60 

    Rated current

     A

    3150

    Rated power frequency withstand voltage (1min) KV

     Isolating

    200

     To ground

    160

    Rated lightning impulse withstand voltage (1min) KV

     Isolating

    410

     To ground

    350

    Rated short-circuit breaking current

    KA 

     31.5

    Rated withstand current(peak)

    KA 

     80

    Rated short-time withstand current(3s)

    KA 

    31.5

    Rated short-circuit making current(peak)

    KA 

     80

    Phase to phase spacing

    mm

    1200

    Moving contactor travel

    mm

    120

    Moving contactor overtravel

    mm

    25

    Opening time

    ms

    40

    Closing time

    ms

    100

    Trip time

    ms

    60

    First pole to clear factor

     

    1.5

    Rated out-of-phase breaking current

    KA

    8

    Short-line fault breaking capability

    KA

    90%IK/75%IK

    Rated line-charging breaking current

    A

    10

    Rated operation sequence

     

    O-0.3s-CO-180s-CO

    Main circuit resistance

    μΩ

    ≤55

    Rated SF6 gas pressure(20℃)

    Mpa

    0.5

    Rated minimum SF6 gas pressure(20℃)

    Mpa

    0.45

    SF6 gas leakage rate(yearly)

    Mpa

    ≤0.5%

    Gas moisture content

    ppm

    ≤150

    Mechanism life

     times

     10000

    Radio interference

     μV

     <500

    Creepage distance (mm)

     Isolating

    2585

     To ground

    2248

    Control system voltage

    V

    220DCV/ACV

    Mass of filled SF6 gas

     Kg

    10

    Mass of equipment

    Kg

    1500

    Dimension  W*D*H

    mm

    4100*2500*4200