FLN36-12 Indoor load break switch (LBS) 12KV

FLN36-12 type indoor high voltage AC load breaker switch refer to international new technology and develop the switching equipment in according to the relevant standards in China's electric power system. Its performance indicators in full compliance IEC420, 694,129 and national standards GB3804-2004.

This is the main switching element RMU. The load breaker switch is a multifunctional medium voltage switchgear of gates, sub-gate, earthing. In a fully sealed with strengthen the structure of the epoxy resin housing to filled with SF6 gas,0.05MPa, with the minimum parts to achieve the above three functions, to ensure product quality, improve reliability, maintenance-free. It can be safely run for more than 20 years in normal conditions.

    Environment condition

    1. The altitude: under 1000M.
    2. The ambient temperature: -25℃-+40℃.
    3. The relative humidity of air: monthly≤90%, daily≤95%.
    4. Amplitude: Earthquake degree 8.
    5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

     

     

     

     

     

     

    Technical parameter

    Technical Name

    Unit

    Model

    FLN36-12/630

    FLRN36-12D/125-31.5 

    With switch-fuse

    1

        Rated voltage

    KV

    12

    2

        Rated Frequency

    Hz

    50

    3

        Rated current

    Amp

    630

    125

    4

        Rated Insulation 

    Level

    L min power-frequency 

    withstand voltage (KV)

    42

    48

    Lighting impulse 

    withstand voltage(Peak) KV

    75

    85

    5

       Rated thermal current (2S)

    KA

    20

     

    6

       Rated dynamic current

    KA

    50

    7

        Rated short-circuit on-off current

    KA

    25

    8

       Rated closed loop breaking current  

    A

    630

    9

    Rated active on-load breaking current

    A

    630

    10

    Rated cable charger breaking current

    A

    10

    11

    Rated short-circuit breaking current

    (peak)

    KA

     

    50

    12

    Impact output energy

    J

    1+0.5

    13

       Rated thermal current(2S)for 

    grounding switch

    KA

    2

    14

      Rated dynamic current (peak)for 

    grounding switch

    KA

    Maximum torque 

    operated manually  

    15

       Rated short-circuit on-off current for 

    grounding switch

    KA

    50

    2

               

     

    1.png