Inquiry
Form loading...
Products Categories
Featured Products

FN7-12 Indoor load break switch (LBS) 12KV

FN7- 12R(L) model indoor AC HV load break switch-fuse combination apparatus is developed and designed based on international technology and national power supply requirement, it passed all type tests and trial-operation inspections. The apparatus conforms to IEC420: AC LOAD BREAK SWITCH AND  FUSE COMBINATION APPARATUS(1990 EDITION) Compared to international product it keeps up with technical level with small volume and light weight. It is applicable in ring main unit and prefabricated substations as well as 12kv line and power distribution system. The product realizes three working positions: power making. power breaking and earth. It applies to power system of rated voltage 6- 12kv, 50/60HZ breaking load current over load current and short-circuit current.

    Environment condition

    1. The altitude: under 1000M.
    2. The ambient temperature: -25℃-+40℃.
    3. The relative humidity of air: monthly≤90%, daily≤95%.
    4. Amplitude: Earthquake degree 8.
    5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

     

     

    Technical parameter

    NO

    Item

    Units

    Technical parameters

    1

    Rated voltage

    kV

    10

    2

    Maximum working voltage

    kV

    12

    3

    Rated current

    A

    200

    400

    630

    4

    Rated short-time withstand current(4s)

    kA

    6

    12.5

    20

    5

    Rated peak withstand current

    kA

    15

    31.5

    50

    6

    Rated closed loop breaking current

    A

    200

    400

    630

    7

    Rated loading breaking current

    A

    200

    400

    630

    8

    Rated loading breaking current (5%)

    A

    10

    20

    31.5

    9

    Rated short circuit closing current

    kA

    15

    31.5

    50

    10

    Power frequency withstand voltage

    kV

    42(Fracture:48)

     Lightning impulse withstand voltage

    75(Fracture:84)

    11

    Open/close operating torque

     N.m(N)

    90(180)

    100(200)

                 

     

    N5.jpg