Inquiry
Form loading...
Products Categories
Featured Products

FZN16-12 Indoor load break switch (LBS) 12KV

FZN16 is a kind of indoor high voltage vacuum load switch, suitable for three-phase AC 50Hz power grid with rated voltage 6-12KV, mainly used to break load current, overload current and short circuit current. ‌ This kind of switch is especially suitable for oil-free, no maintenance and frequent operation requirements ‌.

The FZN16 load switch can be used with CS6-I operating mechanism and CS□ manual operating mechanism to meet different operation requirements. It is designed with frequent operation in mind and therefore performs well in situations where high frequency operations are required ‌. In addition, the FZN16 load switch also has the characteristics of no maintenance, reducing the need for maintenance work, improve the reliability of the equipment ‌.

    Environment condition

    1. The altitude: under 1000M.
    2. The ambient temperature: -25℃-+40℃.
    3. The relative humidity of air: monthly≤90%, daily≤95%.
    4. Amplitude: Earthquake degree 8.
    5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

     

     

     

     

     

    Technical parameter

    No

    Item

    Unit

    Value

    1

    Rated voltage

    kV

    12

    2

    Rated frequency

    Hz

    50

    3

    Rated current

    A

    630

    125

    4

    Rated insulation level

    1min power frequency withstand voltage

    kV

    Arc-quenching chamber

    fracture 30

    Effective value

    Earth , phase 42,

    insulating fracture 48

    Lightning impulse withstand voltage (peak)

    Earth , phase 75,

    insulating fracture 85

    5

    Rated dynamic current (peak)

    kA

    50

    6

    4S thermal current

    kA

    20

    7

    Rated power load breaking current

    A

    630

    8

    Rated closed-loop breaking current

    A

    630

    9

    Rated cable charge breaking current

    A

    10

    10

    Rated breaking no-load transformer capacity

    kV

    1250

    11

    Rated breaking AC current

    A

    3150

    12

    Rated short-circuit closed current

    kA

    50

    13

    Rated current breaking times

    times

    2000

    14

    Mechanical life

    times

    10000

    15

    Permitted wear-thickness of  vacuum arc-quenching chamber contact

    mm

    2

    16

    Manual operating torque

    Nm

    >200