FZN21-12 Indoor load break switch (LBS) 12KV

FZN21-12 type of indoor AC high voltage load switch- fuse combination units appliances for three-phase AC 10kV, 50Hz power system, or with the complete power distribution equipment and loop-network switch cabinet , combined substation and other ancillary uses, is widely used in urban network construction and transformation engineering, industrial and mining enterprises, high-rise buildings and public facilities ,can be used as ring power supply unit or terminal equipment, play power distribution, control and protection. Technical performance of the products meet the IEC publication 60265-1/FDIS

    Structural features

    1. load switch, grounding switch, fuse and instructions in a framework that can be flexibly combined, compact, convenient and easy to install a small volume.
    2. the fracture is direct acting arrangement. dynamic and thermal stability current parameters is high, time to complete the operation. 
    3. with static contact insulation cover, so RMU in the structure to achieve the isolation, eliminating the phase insulating spacer, fracture insulation boards that can prevent internal arc short circuit accident.
    4. has a unique valve structure, load switch after opening the shutter automatically fracture isolation, good protective properties. 
    5. load switch and grounding switch, a reliable mechanical locking device between the fuse. to meet the "Five Anti requirements.

    Two forms of electric operations 6, with manual operation and AC and DC operating power supply, easy to implement power system, "three remote' requirements.

    Technical parameter

    No

    Item

    Unit

    Value

    1

    Rated voltage

    kV

    12

    2

    Rated frequency

    Hz

    50

    3

    Rated current

    A

    630

    125

    4

    Rated insulation level

    1min power frequency withstand voltage

    kV

    Arc-quenching chamber

    fracture 30

    Effective value

    Earth , phase 42,

    insulating fracture 48

    Lightning impulse withstand voltage (peak)

    Earth , phase 75,

    insulating fracture 85

    5

    Rated dynamic current (peak)

    kA

    50

    6

    4S thermal current

    kA

    20

    7

    Rated power load breaking current

    A

    630

    8

    Rated closed-loop breaking current

    A

    630

    9

    Rated cable charge breaking current

    A

    10

    10

    Rated breaking no-load transformer capacity

    kV

    1250

    11

    Rated breaking AC current

    A

    3150

    12

    Rated short-circuit closed current

    kA

    50

    13

    Rated current breaking times

    times

    2000

    14

    Mechanical life

    times

    10000

    15

    Permitted wear-thickness of  vacuum arc-quenching chamber contact

    mm

    2

    16

    Manual operating torque

    Nm

    >200