Inquiry
Form loading...
Products Categories
Featured Products

FZN63-12 Indoor load break switch (LBS) 12KV

FZN63-12 is a high voltage vacuum load switch, mainly used to control and protect high voltage equipment in power systems. ‌ Its main functions include switching operation and overload protection, through the vacuum interrupter to achieve quick power off and coincidence operation, improve the reliability and safety of power supply ‌.

    The FZN63-12 high-pressure vacuum load switch has the following specific functions:

    ‌Switch operation:through the vacuum interrupter to realize the circuit opening and closing, suitable for frequent operation environment.

    ‌Overload protection:with overload protection function, can quickly cut off the circuit when the overload current is detected to prevent equipment damage.

    ‌‌High reliability: using vacuum arc extinguishing technology, has the characteristics of long life, low maintenance, suitable for all kinds of harsh environment ‌.

    Environment condition

    1. The altitude: under 1000M.
    2. The ambient temperature: -25℃-+40℃.
    3. The relative humidity of air: monthly≤90%, daily≤95%.
    4. Amplitude: Earthquake degree 8.
    5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

     

     

    Technical parameter

    No

    Item

    Unit

    Value

    1

    Rated voltage

    kV

    12

    2

    Rated frequency

    Hz

    50

    3

    Rated current

    A

    630

    125

    4

    Rated insulation level

    1min power frequency withstand voltage

    kV

    Arc-quenching chamber

    fracture 30

    Effective value

    Earth , phase 42,

    insulating fracture 48

    Lightning impulse withstand voltage (peak)

    Earth , phase 75,

    insulating fracture 85

    5

    Rated dynamic current (peak)

    kA

    50

    6

    4S thermal current

    kA

    20

    7

    Rated power load breaking current

    A

    630

    8

    Rated closed-loop breaking current

    A

    630

    9

    Rated cable charge breaking current

    A

    10

    10

    Rated breaking no-load transformer capacity

    kV

    1250

    11

    Rated breaking AC current

    A

    3150

    12

    Rated short-circuit closed current

    kA

    50

    13

    Rated current breaking times

    times

    2000

    14

    Mechanical life

    times

    10000

    15

    Permitted wear-thickness of  vacuum arc-quenching chamber contact

    mm

    2

    16

    Manual operating torque

    Nm

    >200

    LW8.jpg