Outdoor disconnector,CE Certified Outdoor Disconnector Switch FactoryGW13-40.5 Outdoor disconnector of neutral point
product detail
Service Conditions:
- Altitude:1500m
- Ambient temperature:-45°C ~45°C
- Wind pressure:≤700pa(wind speed 34m/s)
- Earthquake intensity:≤8 degree
- Humidity of air:monthly≤90°C,daily≤95°C
- Environment degree: degree III
- Cannot be use on the condition of the danger of fire and blast,heavy pollution,chemical etching,strong shake ect.
Technical parameter
|
Rated voltage kV |
40.5 |
|
|
Rated current A |
400, 630, |
|
|
Rated peak withstand current kA |
Disconnector |
80, |
|
Earthing switch |
80 |
|
|
Rated short-time withstand current and duration kA/s |
Disconnector |
31.5 |
|
Earthing switch |
31.5 |
|
|
Rated short-time power frequency withstand voltage (rms.) kV |
To earth |
95 |
|
Between breaks |
118 |
|
|
Rated lightning impulse withstand voltage (peak) kV |
To earth |
185 |
|
Between breaks |
215 |
|
|
Mechanical life |
times |
2000 |
|
Rated mechanical load of the terminal |
mm |
400 |
|
Leakage distance |
fxQ |
<160 |
|
Mechanism |
Model No. |
Cs 17 OR CJ6,CK7 |
|
Weight |
KG |
140*3 |