Inquiry
Form loading...
Products Categories
Featured Products

Outdoor disconnector,CE Certified Outdoor Disconnector Switch FactoryGW13-72.5 Outdoor disconnector of neutral point 72.5kv

GW13-72.5 Outdoor disconnector of neutral point 72.5kv

GW13-72.5 Isolation switch is a high-voltage switchgear commonly used in power systems, mainly used to isolate the power supply, change the operating mode, and perform circuit maintenance isolation measures. ‌ It has the advantages of simple structure, convenient operation and less maintenance, and plays an important role in the power system ‌.

    product detail

    1、The operation mode of the neutral point is different, and its technical characteristics and working conditions are also different, so the influence and requirements on the reliability of operation, equipment insulation and its protection measures are also different.

    2、The transformer neutral point gap grounding protection device is specially used for the neutral point of 110KV, 220KV, 330KV, 500KV power transformers, and is designed to realize two different operation modes of neutral point grounding or non-grounding, so as to avoid Due to lightning strikes and faults, the voltage rises at the neutral point and damages the insulation of the transformer.

    3、This product can be widely used in electric power, metallurgy, chemical industry and coal industry.

     

     

     

     

     

     

    Technical parameter

    Rated voltage kV

    72.5

    Rated current A

    400, 630,

     Rated peak withstand current kA 

    Disconnector

    80,

    Earthing switch

    80

     Rated short-time withstand current and duration kA/s 

    Disconnector

    31.5

    Earthing switch

    31.5

    Rated short-time power frequency withstand voltage (rms.) kV 

    To earth

    140

    Between breaks

    160

    Rated lightning impulse withstand voltage (peak) kV 

    To earth

    325

    Between breaks

    375

    Mechanical life

    times

    2000

    Rated mechanical load of the terminal

    mm

    675

    Leakage distance

    fxQ

    <180

    Mechanism

    Model No.

    Cs 17 OR CJ6,CK7

    Weight

    KG

    160*3