Inquiry
Form loading...
Products Categories
Featured Products

Outdoor disconnector,CE Certified Outdoor Disconnector Switch FactoryGW5-40.5 Outdoor disconnector(isolate switch)40.5kv

GW5-40.5 Outdoor disconnector(isolate switch)40.5kv

GW5 is a double-column horizontal fracture center opening type, and a grounding switch can be attached to one or both sides. The isolating switch of 90° transmission adopts CS17 type manual operation mechanism for three-pole linkage operation; the isolation switch of 180° transmission adopts CJ6 type motor operation mechanism or CS17G type manual operation mechanism for three-pole linkage operation; the grounding switch adopts CS17G type manual operation mechanism. The three-pole linkage operation of the driving mechanism.

Product feature

1.Complete in specifications,high technical parameters is high, wide range. Additional, wide scope of application , it can be used for high layout. Installation way is flexible. 

2.Perfect sealing Performance and  Resistant To Rust 

3.Simple, reliable mechanical rotating way. 

4.Perfect dustproof, waterproof, and anti-corrosion ability. 

5.Full set of steel galvanized foundation frame and the vertical and horizontal  dwang for option.

    product detail

     

    Service Conditions:

    • Altitude:1500m
    • Ambient temperature:-45°C ~45°C
    • Wind pressure:≤700pa(wind speed 34m/s)
    • Earthquake intensity:≤8 degree
    • Humidity of air:monthly≤90°C,daily≤95°C
    • Environment degree: degree III
    • Cannot be use on the condition of the danger of fire and blast,heavy pollution,chemical etching,strong shake ect.

     

     

     

     

     

     

    Technical parameter

    Rated voltage kV

    40.5

    Rated current A

    1250, 2000,

     Rated peak withstand current kA 

    Disconnector

    100,

    Earthing switch

    100

     Rated short-time withstand current and duration kA/s 

    Disconnector

    50/3

    Earthing switch

    50/3

    Rated short-time power frequency withstand voltage (rms.) kV 

    To earth

    95

    Between breaks

    118

    Rated lightning impulse withstand voltage (peak) kV 

    To earth

    185

    Between breaks

    215

    Creepage distance

    mm

    1025~1250

    Mechanical life

    times

    2000

    Motor supply power

    V

    ACV380

    Control system voltage

    V

    AC/DC 220V

    Small capacitive current during opening and closing A

    1

    Small inductive current during opening and closing A

    0.5

    Radio interference level μV

    ≤2500

     Rated static mechanical load of the terminal N 

    Horizontal longitudinal direction

    1000

    Horizontal transverse direction

    750

    Vertical force

    750

    Weight

    KG

    360~460