JCZ5-12 Indoor vacuum contactor 12KV (fixed)

JCZ5-12 vacuum contactor is suitable for AC 50-60Hz main circuit rated working voltage of 7.2kV, 12kV, rated current of 630A below the power network for remote connection and breaking and frequent start and control of AC motor, more suitable and fuse and various protection devices to replace the vacuum circuit breaker.

    1. JCZ5 vacuum contactor is composed of insulation frame, metal base, transmission arm, electromagnetic system, auxiliary switch and vacuum arc extinguishing chamber. When the electromagnetic coil passes the control voltage, the armature drives the crank arm to turn, so that the main contact in the vacuum interrupter room is connected, and the main contact is broken after the electromagnetic coil is powered off due to the action of the opening spring.
    2. The vacuum arc extinguishing chamber is composed of an upper cover, a lower cover, a metal bellows and a ceramic tube. The shell is made of corrugated porcelain tubes made of 95 porcelain insulating materials. It has the characteristics of large creepage distance, high mechanical strength, heat resistance and impact resistance.

    3, the electromagnetic system considers the actual suction characteristics and reaction characteristics of good coordination, as well as the contactor to play the advantages of low noise and power saving, the use of DC double coil by starting and maintaining two windings,

    4, mechanical lock: when the closing coil is energized, the contactor is closed, the mechanical lock is locked, when the trip coil is energized, the mechanical lock is released, the contactor is released, the trip coil is in a hot state, the voltage is in the range of Ue85%-110% to make the contactor reliable release.

     

    Technical parameters:

    NO.

    Parameters

    Unit

    Value

    BKZC(R)-12-630/400/250

    BKZC(R)-12-630/400/250

    1

    Rated Voltage

    kV

    7.2

    12

    2

    Rated Current

    A

    630

    400

    250

    630

    400

    250

    3

    Rated closing current (rms)

    A

    6300

    4000

    2500

    6300

    4000

    2500

    4

    rated breaking current

    5040

    3200

    2500

    5040

    3200

    2500

    5

    4S thermal current

    6300

    4000

    2500

    6300

    4000

    2500

    6

    Limit breaking current

    6300

    4000

    2500

    6300

    4000

    2500

    7

    Power frequency withstand voltage

    kV

    32

    42

    8

    operating frequency

    Times/h

    300

    9

    Electric life time

    AC-3

    ×10Times

    25

    AC-4

    10

    10

    Mechanical life

    30

    11

    Rated operating voltage

    V

    AC110/220

    12

    Closing coil pull current

    A

    ≤ DC6/3

    13

    Holding coil holding current

    D:DC0.32/0.16

    14

    Shunt trip coil current

    J:DC2.5/1.3