JCZ8-12 Indoor vacuum contactor 12KV (fixed)

The main function of the high-pressure vacuum contactor is to operate the large load current frequently, especially suitable for harsh environment and flammable and explosive dangerous places.

The working principle of the high pressure vacuum contactor is similar to that of the low pressure contactor, the contactor is drawn by charging the coil, and the contactor returns when the coil is out of power. The main difference is that the high-pressure vacuum contactor can be operated on and off in a vacuum environment, and the vacuum arc extinguishing chamber is used to extinguish the arc, which is suitable for the on-off of high voltage and large current.

    The high voltage vacuum contactor is designed to operate without protection, similar to the switch on a household light, it cannot disconnect the short circuit current, so it is often used in conjunction with a high voltage vacuum circuit breaker to provide more comprehensive circuit protection. Because of its small size, light weight, frequent operation and other characteristics, this equipment is widely used in a variety of frequent operation fields, including power system, metallurgy, mining, rolling stock, rail transit and other industries of high voltage equipment, to ensure the safety of equipment and personnel.

     

    1.png

     

     

    Technical parameters:

    NO.

    Parameters

    Unit

    Value

    BKZC(R)-12-630/400/250

    BKZC(R)-12-630/400/250

    1

    Rated Voltage

    kV

    7.2

    12

    2

    Rated Current

    A

    630

    400

    250

    630

    400

    250

    3

    Rated closing current (rms)

    A

    6300

    4000

    2500

    6300

    4000

    2500

    4

    rated breaking current

    5040

    3200

    2500

    5040

    3200

    2500

    5

    4S thermal current

    6300

    4000

    2500

    6300

    4000

    2500

    6

    Limit breaking current

    6300

    4000

    2500

    6300

    4000

    2500

    7

    Power frequency withstand voltage

    kV

    32

    42

    8

    operating frequency

    Times/h

    300

    9

    Electric life time

    AC-3

    ×10Times

    25

    AC-4

    10

    10

    Mechanical life

    30

    11

    Rated operating voltage

    V

    AC110/220

    12

    Closing coil pull current

    A

    ≤ DC6/3

    13

    Holding coil holding current

    D:DC0.32/0.16

    14

    Shunt trip coil current

    J:DC2.5/1.3