LW25-252 4000-50 outdoor circuit breaker 252KV
This product uses SF6 gas as the arc extinguishing insulating medium, adopts the world's most advanced self-energy arc extinguishing technology, and is equipped with a new spring operating mechanism, long electrical life, low running power, low noise, high reliability, simple structure, small volume, long maintenance cycle. In the current process of power equipment towards oil-free and large capacity, it can completely replace the same type of imported products.
Operating condition
Temperature :-10℃~ + 40℃
Relative humidity: the daily average relative humidity is not more than 95%; The average monthly relative humidity does not exceed 90%
Earthquake intensity: not more than 8.
Saturated vapor pressure: the daily average pressure does not exceed 2.2kPa, the monthly average pressure does not exceed 1.8Kpa
Altitude :≤1000m(except for special circumstances)
The device should be installed in a place without fire, explosion, serious dirt, chemical erosion, and violent vibration.
Technical parameter
|
Item |
Unit |
Data |
|
Rated voltage |
KV |
252 |
|
Rated power frequency |
Hz |
50/60 |
|
Rated current |
A |
4000 |
|
Rated power frequency withstand voltage (1min) KV |
Isolating |
460+146 |
|
To ground |
460 |
|
|
Rated lightning impulse withstand voltage (1min) KV |
Isolating |
1050+206 |
|
To ground |
1050 |
|
|
Rated short-circuit breaking current |
KA |
40/50 |
|
Rated withstand current(peak) |
KA |
125 |
|
Rated short-time withstand current(3s) |
KA |
40/50 |
|
Rated short-circuit making current(peak) |
KA |
125 |
|
Phase to phase spacing |
mm |
3000-4000 |
|
Moving contactor travel |
mm |
160 |
|
Moving contactor overtravel |
mm |
50 |
|
Opening time |
ms |
30 |
|
Closing time |
ms |
90 |
|
Trip time |
ms |
60 |
|
First pole to clear factor |
|
1.3 |
|
Rated out-of-phase breaking current |
KA |
12.5 |
|
Short-line fault breaking capability |
KA |
90%IK/75%IK |
|
Rated line-charging breaking current |
A |
200 |
|
Rated operation sequence |
|
O-0.3s-CO-180s-CO |
|
Main circuit resistance |
μΩ |
≤55 |
|
Rated SF6 gas pressure(20℃) |
Mpa |
0.6 |
|
Rated minimum SF6 gas pressure(20℃) |
Mpa |
0.55 |
|
SF6 gas leakage rate(yearly) |
Mpa |
≤0.5% |
|
Gas moisture content |
ppm |
≤150 |
|
Mechanism life |
times |
10000 |
|
Radio interference |
μV |
<500 |
|
Creepage distance (mm) |
Isolating |
8660 |
|
To ground |
6900 |
|
|
Heating and lighting voltage |
V |
220ACV |
|
Control system voltage |
V |
220DCV/ACV |
|
Mass of filled SF6 gas(single pole) |
Kg |
8 |
|
Mass of equipment(single pole) |
Kg |
1500 |
|
Dimension (single pole) W*D*H |
mm |
700*650*6920 |