SF6 Load Break Switch 12KV 24KV 36KV FLN36-12 indoor load breaker switch

FLN36-12 type indoor high voltage load breaker switch

Environment condition


1. The altitude: under 1000M.


2. The ambient temperature: -25℃-+40℃.


3. The relative humidity of air: monthly≤90%, daily≤95%.


4. Amplitude: Earthquake degree 8.


5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

    product detail

    Product Description

    FLN36-12 indoor load breaker switch

    Product Description

    FLN36-12 type indoor high voltage AC load breaker switch refer to international new technology and develop the switching equipment in according to the relevant standards in China's electric power system. Its performance indicators in full compliance IEC420, 694,129 and national standards GB3804-2004“3.6kV-0.5kV high voltage AC load breaker switch" GB1985-2004“high-voltage AC isolation switch and earthing switch" GB/ T1 1022-1999“common technical requirements for high-voltage switchgear and control equipment standards" . This is the main switching element RMU. The load breaker switch is a multifunctional medium voltage switchgear of gates, sub-gate, earthing. In a fully sealed with strengthen the structure of the epoxy resin housing to filled with SF6 gas,0.05MPa, with the minimum parts to achieve the above three functions, to ensure product quality, improve reliability, maintenance-free. It can be safely run for more than 20 years in normal conditions.

    Environment condition

    1. The altitude: under 1000M.

    2. The ambient temperature: -25℃-+40℃.

    3. The relative humidity of air: monthly≤90%, daily≤95%.

    4. Amplitude: Earthquake degree 8.

    5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

    Products features

    1.Load breaker switch adapts double fracture, rotary movable contact structure, with the following three kinds of operating states: Closing,opening, earthing.

    2.Uusing SF6 gas as an arc extinguishing and insulating medium, the main circuit seals by the upper and lower housing pouring epoxy rein, the conductive function is unaffected by external influences.

    3.Good safety performance. If internal arcing occurs, the housing has an internal structure weak point, it will be rushed to open, followed by the cabinet above the shutter release arc red open air overpressure stream-oriented outside the cabinet, ensure that the switch cabinet security checks.

    4.Load breaker switch sets gates, opening, earthing switch three at one, filled with SF6 gas encapsulated in epoxy resin housing, three-position interlock, compact structure, high security and reliability.

    5.Small size, light weight, maintenance-free, easy and safe to operate.

     Technical parameter

    Technical Name

    Unit

    Model

    BRFLN36-12/630

    BRFLN36-12D/125-50 

    switch-fuse combinations

    1

        Rated voltage

    KV

    12

    2

        Rated Frequency

    Hz

    50

    3

        Rated current

    Amp

    630

    125

    4

        Rated Insulation 

    Level

    L min power-frequency 

    withstand voltage (KV)

    42

    48

    Lighting impulse 

    withstand voltage(Peak) KV

    75

    85

    5

       Rated thermal current (2S)

    KA

    20

     

    6

       Rated dynamic current

    KA

    50

    7

        Rated short-circuit on-off current

    KA

    25

    8

       Rated closed loop breaking current  

    A

    630

    9

    Rated active on-load breaking current

    A

    630

    10

    Rated cable charger breaking current

    A

    10

    11

    Rated short-circuit breaking current(peak)

    KA

     

    50

    12

    Rated transfer current

    A

    1700

    13

    Fuse type

     

    Sfldj-12

    14

    Impact output energy

    J

    1+0.5

    15