Product Description
BKV3(VS1)-24KV vacuum circuit breaker
The BKV3-24 indoor H.V. vacuum circuit breaker is a three-phase indoor switchgear with a rated voltage of 24 kV. It provides control and protection for power plants, substations, electrical facilities, and industrial and mining enterprises. Its integrated design uses a VET operating mechanism and can be used as a fixed installation unit or as a mobile unit with a special advance mechanism. The handcart unit is composition uses some of the main circuit and can utilize the entire solid seal post with great reliability and requires no maintenance. To achieve smaller circuit breakers, it can be equipped with KYN28A 24 and other handcart switch cabinets. It can also be utilized in the house with fixed XGN switchgear.
VS1-Series circuit breaker features high stability and high reliability
Vacuum circuit breakers of the VS1-Series are engineered with unique transmission part optimization. The benefits of modular spring mechanisms include easy maintenance, quick power-off maintenance, high component diversity, and superior compatibility with vacuum interrupters, which significantly raises the technical specifications and yields even higher performance.
Applicable standards
1EC62271-100 High-voltage switchgear and control-gear-Part 100: Alternating-current circuit-breakers
Secondary circuit
The secondary control circuit boards of vacuum circuit breakers of the VS1-Series are modularly designed. High-grade self-fastener plugs are used for the mechanisms' electric connection, which makes replacement easier and guarantees a dependable electrical connection. * Superior functioning oil buffer
High-performance oil buffer
A high-performance breaking buffer can prevent mechanical endurance loss from partial overstress of vacuum interrupter bellows caused by moving contact overshoot by significantly reducing the overshoot and rebounding amplitudes of the moving contact of a vacuum circuit breaker during breaking. No re-ignition or restrike is detected during the switching capacitor bank test as the moving contact's rebounding amplitudes decrease.
|
Item
|
Unit
|
20kA
|
25kA
|
31.5kA
|
40kA
|
|
Rated Voltage
|
kV
|
20
|
|
Max working voltage
|
kV
|
24
|
|
Rated Current
|
A
|
630
|
1250
|
1250
1600
2500
3150
|
1250
1600
2500
3150
|
|
Rated short circuit breaking current
|
kA
|
20
|
25
|
31.5
|
40
|
|
Rated short circuit making current (peak)
|
kA
|
50
|
63
|
80
|
100
|
|
Rated peak withstand current
|
kA
|
50
|
63
|
80
|
100
|
|
4s rated short time withstand current
|
kA
|
20
|
25
|
31.5
|
40
|
|
Rated insulation
level
|
Power frequency withstand voltage
|
kV
|
62(fracture65)
|
|
Impulse withstand voltage
|
121(fracture125)
|
|
Rated sequence of operation
|
|
0-0.3s-CO-180s-CO
|
|
Mechanical life
|
time
|
10000
|
|
Breaking times of rated short circuit breaking current
|
time
|
50
|
|
Operating voltage
|
V
|