• ZW43 12kv circuit breaker ac vacuum switch
  • ZW43 12kv circuit breaker ac vacuum switch
  • ZW43 12kv circuit breaker ac vacuum switch
  • ZW43 12kv circuit breaker ac vacuum switch
  • ZW43 12kv circuit breaker ac vacuum switch

ZW43 12kv vacuum circuit breaker

ZW43 12kv circuit breaker ac vacuum switch
They are designed for the construction and reform of urban and rural grid. The bottom of the product has adopted stainless steel and galvanized carbon steel with ultraviolet-proof coating material, to make sure it’s normal outdoor operation. Each stainless steel component can ensure it’s durability, stability, water-proof and salt fog against ability.

Share:

Product Description

ZW43 12kv vacuum circuit breaker

Product Description

ZW43 12kv vacuum circuit breaker

ZW43-12/T630-20 type outdoor high voltage isolate vacuum switch is a new generation of high voltage electrical equipment developed by both home and overseas advanced technology. Each of the technical performance have reach the standard of GB3804 and IEC.

They are designed for the construction and reform of urban and rural grid. The bottom of the product has adopted stainless steel and galvanized carbon steel with ultraviolet-proof coating material, to make sure it’s normal outdoor operation. Each stainless steel component can ensure it’s durability, stability, water-proof and salt fog against ability.

It has characteristic of small size, light weight, good appearance, easy operation, strong breaking ability, long electrical life maintenance free and obvious fracture. It can adopt manual single-pole operation and also electric, distance operation.

Application:

1.This outdoor high voltage vacuum circuit breaker that the rated voltage of the three-phase ac 50HZ outdoor distribution equipment the rated current 630A~1250A, short-current 20KA.It mainly used for loading current, overcorrect and short current which use cut-off and close-open electricity system-
2. Suitable for industrial and mining establish company. The aim is to protect and control the system and easy to suitable the rural and some frequent operation place.

Ambient condition

1 Ambient temperature: max +40°C min -40°C

2 Altitude: ≤2000m

3 Wind pressure: ≤700Pa(equals to wind speed 34m/s)

4 Relative humidity: daily average relative humidity: ≤95%; monthly average relative humidity≤90%

5 Air contamination degree: IV degree

6 Earthquake intensity: ≤8 degree, no frequent violent vibration.

 

Main technical parameters 

Serial number

Project

Unit

Parameter

1

Rated voltage

KV

12

2

Rated frequency

Hz

50/60

3

Rated Current

A

630-1250

4

Rated short-circuit breaking current

KA

20

5

Rated peak withstand current(peak)

KA

50

6

Rated short-time Withstand current

KA

20

7

Rated short circuit making current (peak)

KA

50

8

Mechanical life

Times

10000

9

Rated short-circuit breaking current   breaking number Times

Times

30

10

power frequency withstand voltage   (1min):(wet) (dry) Phase, on the ground / Fracture

KV

42/48

11

Lightning impulse withstand voltage(peak)   Phase, on the ground/Fracture

KV

75/85

12

2 Times Loop 1min frequency voltage

KV

2

 


 

 

 

 

  • wechat

    +8613325976739: +8613325976739