SF6 circuit breaker outdoor,AC high-voltage SF6 circuit breaker LW36-126 outdoor circuit breaker 126KV

LW36-126 series outdoor high-voltage SF6 circuit breaker is suitable for outdoor use where the altitude does not exceed 3000m, the ambient temperature is -40℃~ +60℃, and the pollution level does not exceed Class iv. It operates on an AC 50Hz/60Hz network with a maximum voltage of 126kV. Circuit breakers are used to interrupt rated current, fault current or switch lines to control and protect the power system. It can also be used as a disconnect switch.

    product detail

    Operating condition

    Temperature :-10℃~ + 40℃

    Relative humidity: the daily average relative humidity is not more than 95%; The average monthly relative humidity does not exceed 90%

    Earthquake intensity: not more than 8.

    Saturated vapor pressure: the daily average pressure does not exceed 2.2kPa, the monthly average pressure does not exceed 1.8Kpa

    Altitude :≤1000m(except for special circumstances)

    The device should be installed in a place without fire, explosion, serious dirt, chemical erosion, and violent vibration.

     

     

     

    Technical parameter

    Item

    Unit

    Data

    Rated voltage

     KV

     126

    Rated power frequency

     Hz

    50/60 

    Rated current

     A

     3150/2000/1250

    Rated power frequency withstand voltage (1min) KV

     Isolating

    230+70

     To ground

    230

    Rated lightning impulse withstand voltage (1min) KV

     Isolating

    550+100

     To ground

    550

    Rated short-circuit breaking current

    KA 

     40

    Rated withstand current(peak)

    KA 

     100

    Rated short-time withstand current(3s)

    KA 

    40

    Rated short-circuit making current(peak)

    KA 

     100

    Phase to phase spacing

    mm

    1700

    Moving contactor travel

    mm

    150

    Moving contactor overtravel

    mm

    25

    Opening time

    ms

    27

    Closing time

    ms

    100

    Trip time

    ms

    60

    First pole to clear factor

     

    1.5

    Rated out-of-phase breaking current

    KA

    10

    Short-line fault breaking capability

    KA

    36/30

    Rated line-charging breaking current

    A

    31.5

    Rated operation sequence

     

    O-0.3s-CO-180s-CO

    Main circuit resistance

    μΩ

    ≤55

    Rated SF6 gas pressure(20℃)

    Mpa

    0.5

    Rated minimum SF6 gas pressure(20℃)

    Mpa

    0.45

    SF6 gas leakage rate(yearly)

    Mpa

    ≤1%

    Gas moisture content

    ppm

    ≤150

    Mechanism life

     times

     10000

    Radio interference

     μV

     <500

    Creepage distance

     mm

    3150

    Heating and lighting voltage

     V

     220ACV

    Control system voltage

    V

    220DCV/ACV

    Mass of filled SF6 gas(single pole)

     Kg

    4

    Mass of equipment

    Kg

    1800

    Dimension  W*D*H

    mm

    4000*700*5220