SF6 circuit breaker outdoor,SF6 circuit breaker outside,AC high-voltage SF6 circuit breaker LW36-72.5 3150-31.5 outdoor circuit breaker 72.5KV
product detail
Structural characteristics
High performance - rated cycle capacity: strong short circuit breaking capacity at 3150A, -40℃, 40kA.
Long service life - Electrical durability :31.5kA×21times (25kA×31times); Mechanical life: 6000 times without maintenance, up to 10000 times after simple adjustment.
High reliability - sharing arc extinguishing chamber structure with LW36-126; Internal thermal insulation
Redundancy; The whole adopts cast aluminum alloy frame as spring structure; Simple structure, high reliability; Suitable for frequent operations.
Reliable fracture performance.
Reliable sealing performance; Annual leakage of SF6 gas ≤0.5%
Meeting the requirements of hard running environments -suitable for Class IV polluted places and -40℃~+40℃ environments.
Multiple structural forms - usually porcelain post and trolley type.
Technical parameter
|
Item |
Unit |
Data |
|
Rated voltage |
KV |
72.5 |
|
Rated power frequency |
Hz |
50/60 |
|
Rated current |
A |
3150/2500/1250 |
|
Rated power frequency withstand voltage (1min) KV |
Isolating |
160+42 |
|
To ground |
160 |
|
|
Rated lightning impulse withstand voltage (1min) KV |
Isolating |
350+60 |
|
To ground |
350 |
|
|
Rated short-circuit breaking current |
KA |
31.5 |
|
Rated withstand current(peak) |
KA |
80 |
|
Rated short-time withstand current(3s) |
KA |
31.5 |
|
Rated short-circuit making current(peak) |
KA |
80 |
|
Phase to phase spacing |
mm |
1100 |
|
Moving contactor travel |
mm |
150 |
|
Moving contactor overtravel |
mm |
25 |
|
Opening time |
ms |
30 |
|
Closing time |
ms |
150 |
|
Trip time |
ms |
60 |
|
Rated out-of-phase breaking current |
KA |
Ie*25% |
|
Short-line fault breaking capability |
KA |
Ie*75% |
|
Rated operation sequence |
|
O-0.3s-CO-180s-CO |
|
Main circuit resistance |
μΩ |
≤50 |
|
Rated SF6 gas pressure(20℃) |
Mpa |
0.5 |
|
Rated minimum SF6 gas pressure(20℃) |
Mpa |
0.45 |
|
SF6 gas leakage rate(yearly) |
Mpa |
≤1% |
|
Gas moisture content |
ppm |
≤150 |
|
Mechanism life |
times |
10000 |
|
Radio interference |
μV |
<500 |
|
Creepage distance |
mm |
2250 |
|
Heating and lighting voltage |
V |
220ACV |
|
Control system voltage |
V |
220DCV/ACV |
|
Mass of filled SF6 gas(single pole) |
Kg |
4 |
|
Mass of equipment |
Kg |
1000 |
|
Dimension W*D*H |
mm |
2500*700*5660 |