Inquiry
Form loading...
Products Categories
Featured Products

SF6 circuit breaker outdoor,SF6 circuit breaker outside,AC high-voltage SF6 circuit breaker LW36-72.5 3150-31.5 outdoor circuit breaker 72.5KV

LW36-72.5 Self-energizing outdoor high-voltage AC sulfur hexafluoride circuit breaker is an outdoor three-phase porcelain column

Electrical equipment is mainly used in AC 50Hz, 72.5kV extreme cold area of the power system (power station use)

General areas and -40℃ extreme cold areas). This product can be operated frequently and can be used as a connection circuit breaker.

    product detail

    Structural characteristics

    High performance - rated cycle capacity: strong short circuit breaking capacity at 3150A, -40℃, 40kA.

    Long service life - Electrical durability :31.5kA×21times (25kA×31times); Mechanical life: 6000 times without maintenance, up to 10000 times after simple adjustment.

    High reliability - sharing arc extinguishing chamber structure with LW36-126; Internal thermal insulation

    Redundancy; The whole adopts cast aluminum alloy frame as spring structure; Simple structure, high reliability; Suitable for frequent operations.

    Reliable fracture performance.

    Reliable sealing performance; Annual leakage of SF6 gas ≤0.5%

    Meeting the requirements of hard running environments -suitable for Class IV polluted places and -40℃~+40℃ environments.

    Multiple structural forms - usually porcelain post and trolley type.

     

     

     

    Technical parameter

    Item

    Unit

    Data

    Rated voltage

     KV

     72.5

    Rated power frequency

     Hz

    50/60 

    Rated current

     A

     3150/2500/1250

    Rated power frequency withstand voltage (1min) KV

     Isolating

    160+42

     To ground

    160

    Rated lightning impulse withstand voltage (1min) KV

     Isolating

    350+60

     To ground

    350

    Rated short-circuit breaking current

    KA 

     31.5

    Rated withstand current(peak)

    KA 

     80

    Rated short-time withstand current(3s)

    KA 

     31.5

    Rated short-circuit making current(peak)

    KA 

     80

    Phase to phase spacing

    mm

    1100

    Moving contactor travel

    mm

    150

    Moving contactor overtravel

    mm

    25

    Opening time

    ms

    30

    Closing time

    ms

    150

    Trip time

    ms

    60

    Rated out-of-phase breaking current

    KA

    Ie*25%

    Short-line fault breaking capability

    KA

    Ie*75%

    Rated operation sequence

     

    O-0.3s-CO-180s-CO

    Main circuit resistance

    μΩ

    ≤50

    Rated SF6 gas pressure(20℃)

    Mpa

    0.5

    Rated minimum SF6 gas pressure(20℃)

    Mpa

    0.45

    SF6 gas leakage rate(yearly)

    Mpa

    ≤1%

    Gas moisture content

    ppm

    ≤150

    Mechanism life

     times

     10000

    Radio interference

     μV

     <500

    Creepage distance

     mm

    2250

    Heating and lighting voltage

     V

     220ACV

    Control system voltage

    V

    220DCV/ACV

    Mass of filled SF6 gas(single pole)

     Kg

    4

    Mass of equipment

    Kg

    1000

    Dimension  W*D*H

    mm

    2500*700*5660