Vacuum Circuit Breaker(VCB)12KV 24KV 36KV BKZC(R)-12 Drawout type vacuum contactor
We have advanced equipment. Our products are exported to the USA, the UK and so on, enjoying a good reputation among customers for China Manufacturer for 15.6kv Solid Insulated Vacuum Circuit Breaker Sis Vcb (SF6 Free), Since the manufacturing unit founded, we have committed on the advancement of new goods. Together with the social and economic pace, we'll continue to carry ahead the spirit of "high top quality, efficiency, innovation, integrity", and stay with the operating principle of "credit initial, customer 1st, excellent excellent". We are going to create a amazing foreseeable future in hair generation with our partners. China Manufacturer for Sf6 Free Sis and Vcb, If you give us a list of solutions you are interested in, along with makes and models, we can send you quotations. Be sure to email us directly. Our goal is to establish long-term and mutually profitable business relationships with domestic and overseas clients. We look forward to receiving your reply soon.
Product Description
Product Description
BKZC(R)-12 Medium Voltage Drawout type vacuum contactor 400A 630A
Type: AC contactor
Specifications:
vacuum AC contactors utilize vacuum bottle encapsulated contacts to suppress the arc. This arc suppression allows the contacts to be much smaller and use less space than air break contacts at higher currents. As the contacts are encapsulated, vacuum contactors are used fairly extensively in dirty applications, such as mining.
Vacuum contactors are only applicable for use in AC systems. The AC arc generated upon opening of the contacts will self-extinguish at the zero-crossing of the current waveform, with the vacuum preventing a re-strike of the arc across the open contacts. Vacuum contactors are therefore very efficient at disrupting the energy of an electric arc and are used when relatively fast switching is required, as the maximum break time is determined by the periodicity of the AC waveform.
Can be use in KYN28-12 medium voltage metal clad drawout type switchgear assemblies.
Main technical parameters:
|
NO. |
Parameters |
Unit |
Value |
||||||
|
BKZC(R)-12-630/400/250 |
BKZC(R)-12-630/400/250 |
||||||||
|
1 |
Rated Voltage |
kV |
7.2 |
12 |
|||||
|
2 |
Rated Current |
A |
630 |
400 |
250 |
630 |
400 |
250 |
|
|
3 |
Rated closing current (rms) |
A |
6300 |
4000 |
2500 |
6300 |
4000 |
2500 |
|
|
4 |
rated breaking current |
5040 |
3200 |
2500 |
5040 |
3200 |
2500 |
||
|
5 |
4S thermal current |
6300 |
4000 |
2500 |
6300 |
4000 |
2500 |
||
|
6 |
Limit breaking current |
6300 |
4000 |
2500 |
6300 |
4000 |
2500 |
||
|
7 |
Power frequency withstand voltage |
kV |
32 |
42 |
|||||
|
8 |
operating frequency |
Times/h |
300 |
||||||
|
9 |
Electric life time |
AC-3 |
×104 Times |
25 |
|||||
|
AC-4 |
10 |
||||||||
|
10 |
Mechanical life |
30 |
|||||||
|
11 |
Rated operating voltage |
V |
AC110/220 |
||||||
|
12 |
Closing coil pull current |
A |
≤ DC6/3 |
||||||
|
13 |
Holding coil holding current |
D:DC0.32/0.16 |
|||||||
|
14 |
Shunt trip coil current |
J:DC2.5/1.3 |
|||||||
|
NO. |
Parameters |
Unit |
Value |
|
|
BKZC(R)-12-630/400/250 |
BKZC(R)-12-630/400/250 |
|||
|
1 |
contact distance |
mm |
4.5+1.0/-0.5 |
6+1.0-0.5 |
|
2 |
contact overtravel |
1.5±0.5 |
||
|
3 |
Average closing speed |
m/s |
0.1~0.25 |
|
|
4 |
Average opening speed |
0.3~0.6 |
||