Vcb Electrical ,circuit breaker VS1-12 indoor drawout circuit breaker 12kv(insulated cylinder)
product detail
VS1-12 indoor drawout circuit breaker 12kv(insulated cylinder)
VS1-Series insulated cylinder type of drawout VCB generally consists of contact system, arc extinguishing system, operating mechanism, tripping device, shell and so on. "Vacuum circuit breaker" is named after its arc extinguishing medium and the insulating medium of the contact gap after arc extinguishing are both high vacuum; it has the advantages of small size, light weight, suitable for frequent operation, and no need for maintenance of arc extinguishing. The application in the network is more popular. Vacuum circuit breaker is an indoor power distribution device in a 3~10kV, 50Hz three-phase AC system, which can be used as the protection and control of electrical equipment in industrial and mining enterprises, power plants, and substations. It is especially suitable for For places requiring oil-free, less maintenance and frequent operation, circuit breakers can be configured in middle cabinets, double-layer cabinets, and fixed cabinets to control and protect high-voltage electrical equipment.
Technical parameter:
|
NO |
Item |
Units |
Technical parameters |
||||||
|
1 |
Rated voltage |
kV |
12 |
||||||
|
2 |
Maximum working voltage |
kV |
12 |
||||||
|
3 |
Rated current |
A |
630/1250 |
630/1250 |
630/1250/1600 |
||||
|
4 |
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
||||
|
5 |
Rated short circuit closing current |
kA |
50 |
63 |
80 |
||||
|
6 |
Rated peak withstand current |
kA |
50 |
63 |
80 |
||||
|
7 |
4S rated short circuit withstand current |
kA |
20 |
25 |
31.5 |
||||
|
8
|
Rated insulation level |
Power frequency withstand voltage |
kV
|
42(Fracture:48)
|
|||||
|
Impact withstand voltage |
75(Fracture:84) |
||||||||
|
9 |
Rated operation sequence |
0-0.3s-Co-180s-Co |
|||||||
|
10 |
Mechanical life |
times |
10000 |
||||||
|
11 |
Rated short circuit current breaking times |
times |
50 |
||||||
|
12 |
Operating mechanism rated closing voltage |
V |
AC/DC 110,220 |
||||||
|
13 |
Operating mechanism rated trip voltage |
V |
AC/DC 110,200 |
||||||
|
14 |
Moving contactor travel |
mm |
11±1 |
||||||
|
15 |
Moving contactor over-travel |
mm |
3.5±0.5 |
||||||
|
16 |
Three-phase split and close bounce time |
ms |
≤2 |
||||||
|
17 |
Contact closing bounce time |
ms |
≤2 |
||||||
|
18 |
Average opening speed |
m/s |
1.2±0.2 |
||||||
|
19 |
Average closing speed |
m/s |
0.6±0.2 |
||||||
|
20 |
Opening time |
Under max operation voltage |
s |
≤0.05 |
|||||
|
Under min operation voltage |
≤0.08 |
||||||||
|
21 |
Closing time |
S |
0.1 |
||||||
|
22 |
Main loop resistance of each phase |
μΩ |
60 |
50 |
|||||
|
23 |
Dynamic and static contacts allow wear cumulative thickness |
mm |
3 |
||||||