Vcb Electrical ,Vcb circuit breaker VS1-12 indoor fixed vacuum circuit breaker 12kv(insulated cylinder)

It is a 12KV, AC three-phase, 50hz indoor power distribution equipment. It is suitable for the protection and control of equipment in power supply and distribution system such as substation, industrial and mining. The VS1 series vacuum circuit breaker considers reliable interlocking function, can operate frequently at rated current, and has the ability to break short circuit current and fault current many times. This series of vacuum circuit breaker adopts the operating mechanism and the vacuum circuit breaker front and rear arrangement as one. It can be used as a fixed mounting unit, or it can be used with the chassis for independent rails.

    product detail

    It is a 12KV, AC three-phase, 50hz indoor power distribution equipment. It is suitable for the protection and control of equipment in power supply and distribution system such as substation, industrial and mining. The VS1 series vacuum circuit breaker considers reliable interlocking function, can operate frequently at rated current, and has the ability to break short circuit current and fault current many times. This series of vacuum circuit breaker adopts the operating mechanism and the vacuum circuit breaker front and rear arrangement as one. It can be used as a fixed mounting unit, or it can be used with the chassis for independent rails.

    Application environmental condition

    1. Ambient temperature :-10℃ -+ 40℃
    2. Ambient humidity: the average daily humidity is not more than 95%; The average monthly humidity is not more than 90%;
    3. Earthquake intensity: no more than 8 degrees
    4. Saturated steam pressure: the average pressure of a day should not be more than 2. 2kPa, the average monthly pressure should not exceed 1.8kPa;
    5. Altitude :1000m(excluding special requirements)

    6.Should be installed in a place without fire, no explosion, no serious pollution, no chemical corrosion, no violent vibration.

     

     

     

    Technical parameter:

    NO

    Item

    Units

    Technical parameters

    1

    Rated voltage

    kV

    12

    2

    Maximum working voltage

    kV

    12

    3

    Rated current

    A

    630/1250

    630/1250

    630/1250/1600

    4

    Rated short-circuit breaking current

    kA

    20

    25

    31.5

    5

    Rated short circuit closing current

    kA

    50

    63

    80

    6

    Rated peak withstand current

    kA

    50

    63

    80

    7

    4S rated short circuit withstand current

    kA

    20

    25

    31.5

    8

     

    Rated insulation level

    Power frequency withstand voltage

    kV

     

    42(Fracture:48)

     

    Impact withstand voltage

     

                    75(Fracture:84)

    9

    Rated   operation sequence

                              0-0.3s-Co-180s-Co

    10

    Mechanical life

    times

    10000

    11

    Rated short circuit current breaking times

    times

    50

    12

    Operating mechanism rated closing voltage

    V

    AC/DC 110,220

    13

    Operating mechanism rated trip voltage

    V

    AC/DC 110,200

    14

    Moving contactor travel

    mm

    11±1

    15

    Moving contactor over-travel

    mm

    3.5±0.5

    16

    Three-phase split and close bounce time

    ms

    ≤2

    17

    Contact closing bounce time

    ms

    ≤2

    18

    Average opening speed

    m/s

    1.2±0.2

    19

    Average closing speed

    m/s

    0.6±0.2

    20

    Opening time

    Under max operation voltage

    s

    ≤0.05

    Under min operation voltage

    ≤0.08

    21

    Closing time

    S

    0.1

    22

    Main loop resistance of each phase

    μΩ

    60

    50

    23

    Dynamic and static contacts allow wear cumulative   thickness

    mm

    3