Vcb Electrical ,Vcb circuit breaker VS1-12 indoor fixed vacuum circuit breaker 12kv(insulated cylinder)
product detail
It is a 12KV, AC three-phase, 50hz indoor power distribution equipment. It is suitable for the protection and control of equipment in power supply and distribution system such as substation, industrial and mining. The VS1 series vacuum circuit breaker considers reliable interlocking function, can operate frequently at rated current, and has the ability to break short circuit current and fault current many times. This series of vacuum circuit breaker adopts the operating mechanism and the vacuum circuit breaker front and rear arrangement as one. It can be used as a fixed mounting unit, or it can be used with the chassis for independent rails.
Application environmental condition
- Ambient temperature :-10℃ -+ 40℃
- Ambient humidity: the average daily humidity is not more than 95%; The average monthly humidity is not more than 90%;
- Earthquake intensity: no more than 8 degrees
- Saturated steam pressure: the average pressure of a day should not be more than 2. 2kPa, the average monthly pressure should not exceed 1.8kPa;
- Altitude :1000m(excluding special requirements)
6.Should be installed in a place without fire, no explosion, no serious pollution, no chemical corrosion, no violent vibration.
Technical parameter:
|
NO |
Item |
Units |
Technical parameters |
|||||
|
1 |
Rated voltage |
kV |
12 |
|||||
|
2 |
Maximum working voltage |
kV |
12 |
|||||
|
3 |
Rated current |
A |
630/1250 |
630/1250 |
630/1250/1600 |
|||
|
4 |
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
|||
|
5 |
Rated short circuit closing current |
kA |
50 |
63 |
80 |
|||
|
6 |
Rated peak withstand current |
kA |
50 |
63 |
80 |
|||
|
7 |
4S rated short circuit withstand current |
kA |
20 |
25 |
31.5 |
|||
|
8
|
Rated insulation level |
Power frequency withstand voltage |
kV
|
42(Fracture:48)
|
||||
|
Impact withstand voltage |
75(Fracture:84) |
|||||||
|
9 |
Rated operation sequence |
0-0.3s-Co-180s-Co |
||||||
|
10 |
Mechanical life |
times |
10000 |
|||||
|
11 |
Rated short circuit current breaking times |
times |
50 |
|||||
|
12 |
Operating mechanism rated closing voltage |
V |
AC/DC 110,220 |
|||||
|
13 |
Operating mechanism rated trip voltage |
V |
AC/DC 110,200 |
|||||
|
14 |
Moving contactor travel |
mm |
11±1 |
|||||
|
15 |
Moving contactor over-travel |
mm |
3.5±0.5 |
|||||
|
16 |
Three-phase split and close bounce time |
ms |
≤2 |
|||||
|
17 |
Contact closing bounce time |
ms |
≤2 |
|||||
|
18 |
Average opening speed |
m/s |
1.2±0.2 |
|||||
|
19 |
Average closing speed |
m/s |
0.6±0.2 |
|||||
|
20 |
Opening time |
Under max operation voltage |
s |
≤0.05 |
||||
|
Under min operation voltage |
≤0.08 |
|||||||
|
21 |
Closing time |
S |
0.1 |
|||||
|
22 |
Main loop resistance of each phase |
μΩ |
60 |
50 |
||||
|
23 |
Dynamic and static contacts allow wear cumulative thickness |
mm |
3 |
|||||