VS1-12 indoor side mounted circuit breaker 12kv(width 280mm)
product detail
- Pay attention to rated current. Its rated current can generally only be 1250A (under normal circumstances), if the larger current will generally choose formal fixed.
- Breaking short circuit current, its rated breaking short circuit current is generally only 31.5KA, the reason is the same as above.
3.Function: It can also lock, anti-jump and other functions
- On the interlock rod, you can extend left or right
- Spindle can be extended left or right
- Connect incoming and outgoing cables, either left or right. This is different from fixed formal wear.
Environmental conditions:
- Altitude: the altitude does not exceed 1000m;
- Ambient temperature: no higher than +40℃, not lower than -25℃;
- Relative humidity: the daily average does not exceed 95%, and the monthly average does not exceed 90%;
- Earthquake intensity: no more than 8 degrees;
- Locations without fire, explosion hazard, serious contamination, chemical corrosion and severe vibration.
Technical parameter:
NO |
Item |
Units |
Technical parameters |
||||
1 |
Rated voltage |
kV |
10 |
||||
2 |
Maximum working voltage |
kV |
12 |
||||
3 |
Rated current |
A |
630/1250 |
630/1250 |
630/1250 |
||
4 |
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
||
5 |
Rated short circuit closing current |
kA |
50 |
63 |
80 |
||
6 |
Rated peak withstand current |
kA |
50 |
63 |
80 |
||
7 |
4S rated short circuit withstand current |
kA |
20 |
25 |
31.5 |
||
8
|
Rated insulation level |
Power frequency withstand voltage |
kV |
42(Fracture:48) |
|||
Impact withstand voltage |
75(Fracture:84) |
||||||
9 |
Rated operation sequence |
|
0-0.3s-Co-180s-Co |
||||
10 |
Mechanical life |
times |
10000 |
||||
11 |
Rated short circuit current breaking times |
times |
50 |
||||
12 |
Operating mechanism rated closing voltage |
V |
AC/DC 110,220 |
||||
13 |
Moving contactor travel |
mm |
11±1 |
||||
15 |
Moving contactor over-travel |
mm |
3.5±0.5 |
||||
16 |
Average opening speed |
m/s |
1.2±0.2 |
||||
17 |
Average closing speed |
m/s |
0.6±0.2 |
||||
18 |
Closing time |
S |
0.1 |
||||
19 |
Main loop resistance of each phase |
μΩ |
60 |
50 |
|||