Vacuum Circuit Breaker(VCB)12KV 24KV 36KV ZW32-12 outdoor AC vacuum circuit breaker
Our primary intention will be to provide our clientele a serious and responsible small business relationship, giving personalized attention to all of them for Manufacturer of 24kv out Door High Voltage Vacuum Circuit Breaker with Electric Power System, In our efforts, we already have many shops in China and our products have won praise from customers worldwide. Welcome new and old customers to contact us for the future long term business relationships. Manufacturer of Vcb and Vacuum Circuit Breaker, Now we have sufficient experience in producing solutions according to samples or drawings. We warmly welcome customers from home and abroad to visit our company, and to cooperate with us for a splendid future together.
Product Description
Product Description
ZW32-12 model outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit current in 12/24kV, 50/60Hz power system. It is applicable for substations, industry and mining, urban and rural electricity power networks, especially for occasions with frequent operation and automatic power distribution network. It accords with the standard of IEC622 71-100 & GB1984: AC high voltage circuit breaker, IEC60694 & GB/T11022: HV General technical requirement of switch and control apparatus
Service condition
1. Altitude: ≤ 2000m;
2. Ambient temperature: -40°C~+45°C
3. Wind speed: 34m/s
4. Earthquake intensity: ≤8 degree
5. Ambient pollution: IV
6. Ice thickness: 10mm
7. Applicable occasions should be free from inflammables, explosives, corrosives and severe vibrations.
Product technical parameter
Name | Unit | Data | ||
12kV | ||||
Rated voltage | KV | 12 | ||
Rated current | A | 630,1250 | ||
Rated insulating level | 1min.PF withstand voltage | dry | KV | 42(across open contacts:48) |
wet | 34 | |||
Lightning impulse withstand voltage(peak) | kv | 75(across open contacts:85) | ||
Rated short-circuit breaking current | KA | 20,25 | ||
Rated short-circuit making current (peak) | KA | 50,63 | ||
Rated peak withstand current | KA | 50,63 | ||
4s rated short-time withstand current | KA | 20,25 | ||
Rated operating sequence | O-0.3s-CO-180s-CO | |||
Breaking times of rated short-circuit breaking current | times | 30 | ||
Mechanical duration | times | 10000 | ||
Rated voltage of energy storage motor | V | DC or AC220,DC110, 48, 24 | ||
Rated operation voltage | V | DC or AC220,DC110, 48,24 | ||
Abrasions thickness of contacts | mm | 3 | ||
Rated current of over-current release | A | 5 | ||
Current transformer ratio | 200/5, 400/5, 600/5 (Protection degree: Ⅲ class, Class: 0.5) |